# Water quality in South Huntington, NY (Suffolk County)

- Water source: Public water
- Supplier / district: South Huntington Water District
- Supplier contact: South Huntington Water District (https://www.shwd.org/wordpress/wp-content/uploads/2026/05/SHWD-2025-Water-Quality-Report.pdf) — Serves this community per the NYS DOH service-area boundary EPA publishes.
- Supplier contact: Greenlawn Water District (https://www.greenlawnwater.org/wp-content/uploads/2026/05/GWD-2025-ADWQR.pdf) — Also serves about 7% of this community per the NYS DOH service-area boundary.
- Report year: 2025 · Verified: 2026-11-11
- Web page: https://www.fieldstonewater.com/water/south-huntington
- JSON: https://www.fieldstonewater.com/api/v1/towns/south-huntington

Where the report prints both an average and a range, the status column here is judged on the average; where it prints a maximum or a 90th-percentile result, that figure is used. South Huntington Water District's report does not name South Huntington in its service area. The service-area boundary the NYS Department of Health supplies to EPA places most of South Huntington inside the district (https://www.epa.gov/ground-water-and-drinking-water/community-water-system-service-area-boundaries). That mapping is not in the report. The report carries 1 notice: NOTICE OF VIOLATION (monitoring): 'Over the past year our water system failed to conduct required monitoring... During the third quarter of 2025, we did not monitor or test for SOC's from Well No. 19-2 and, therefore, cannot be sure of the quality of your drinking water during that time. It should be noted that all other SOC testing performed throughout the year were either non-detect or well below any MCL. After the missed event, the Suffolk County Dept. of Health was consulted and at the time did not require a notice to be distributed as there was no immediate risk to the consumer.' What is being done: 'Upon discovery, the District reviewed internal procedures, and implemented corrective actions to ensure future resamples are collected on schedule. These actions included implementing a review procedure to flag required resamples for first detects and coordinating with the laboratory to prevent future missed resampling events.' Posted by Michael McGovern; State Water System ID#:5103263. 100% of South Huntington's land lies inside a public water service area (South Huntington Water District and others), per the NYS Department of Health boundaries EPA publishes. A service area is where mains run; a home inside it can still be on a private well.

## Summary

No contaminant averaged above its limit in the reported year.
Individual samples above the limit: Lead (high 15.6 vs limit 15 µg/L).
Detected: Lead, Copper, Barium, Sodium, Chloride, Iron, Nickel, Nitrate, Nitrite, Chromium (total), Sulfate, Zinc, Cyanide, Total Trihalomethanes, Chlorate, 1,1-Dichloroethane, 1,1,1-Trichloroethane, 1,1-Dichloroethene, 1,2-Dichloropropane, cis-1,2-Dichloroethene, Trichloroethene (TCE), Tetrachloroethene (PCE), Trichlorofluoromethane, Gross alpha, Combined Radium 226/228, Free Chlorine, Calcium hardness, Hardness (total), 1,4-Dioxane, PFOS, Lindane, Heptachlor, Formaldehyde, Hexavalent Chromium, PFBA, PFHxS, PFPeA.

## Contaminants

| Contaminant | Average | Range | Unit | Limit | Limit source | Status | Peak above limit | Samples |
|---|---|---|---|---|---|---|---|---|
| Lead | 1.3 | ND to 15.6 | µg/L | 15 | EPA action level | detected | yes | — |
| Copper | 0.2 | 0.0083 to 0.44 | mg/L | 1.3 | EPA action level | detected | no | — |
| Barium | 0.025 | ND to 0.025 | mg/L | 2.0 | EPA MCL | detected | no | — |
| Sodium | 21.9 | 2.9 to 21.9 | mg/L | — | NYS guidance (20 mg/L for sodium-restricted diets) | detected | no | — |
| Chloride | 47.9 | 4.3 to 47.9 | mg/L | 250 | NYS secondary standard | detected | no | — |
| Iron | 0.062 | ND to 0.062 | mg/L | 0.3 | NYS secondary standard | detected | no | — |
| Nickel | 0.0084 | ND to 0.0084 | mg/L | — | No regulatory limit | detected | no | — |
| Nitrate | 7.9 | 0.42 to 7.9 | mg/L | 10 | EPA MCL | detected | no | — |
| Nitrite | 0.092 | ND to 0.092 | mg/L | 1 | EPA MCL | detected | no | — |
| Chromium (total) | 7.2 | ND to 7.2 | µg/L | 100 | EPA MCL | detected | no | — |
| Sulfate | 8.5 | ND to 8.5 | mg/L | 250 | NYS secondary standard | detected | no | — |
| Zinc | 0.051 | ND to 0.051 | mg/L | 5.0 | NYS secondary standard | detected | no | — |
| Cyanide | 11.5 | ND to 11.5 | µg/L | 50 | EPA MCL | detected | no | — |
| Total Trihalomethanes | 8.9 | ND to 8.9 | µg/L | 80 | EPA MCL | detected | no | — |
| Chlorate | 71.7 | ND to 71.7 | µg/L | — | No regulatory limit | detected | no | — |
| 1,1-Dichloroethane | 2.5 | ND to 2.5 | µg/L | 5 | EPA MCL | detected | no | — |
| 1,1,1-Trichloroethane | 0.84 | ND to 0.84 | µg/L | 5 | EPA MCL | detected | no | — |
| 1,1-Dichloroethene | 0.97 | ND to 0.97 | µg/L | 5 | EPA MCL | detected | no | — |
| 1,2-Dichloropropane | 2.5 | ND to 2.5 | µg/L | 5 | EPA MCL | detected | no | — |
| cis-1,2-Dichloroethene | 4.4 | ND to 4.4 | µg/L | 5 | EPA MCL | detected | no | — |
| Trichloroethene (TCE) | 1.7 | ND to 1.7 | µg/L | 5 | EPA MCL | detected | no | — |
| Tetrachloroethene (PCE) | 0.54 | ND to 0.54 | µg/L | 5 | EPA MCL | detected | no | — |
| Trichlorofluoromethane | 1.1 | ND to 1.1 | µg/L | 5 | EPA MCL | detected | no | — |
| Gross alpha | 0.158 | — | pCi/L | 15 | EPA MCL | detected | no | — |
| Combined Radium 226/228 | 1.4 | 0.18 to 1.4 | pCi/L | 5 | EPA MCL | detected | no | — |
| Free Chlorine | 1.5 | 1.0 to 1.5 | mg/L | 40 | EPA MRDL | detected | no | — |
| Calcium hardness | 31.0 | 1.4 to 31.0 | mg/L | — | No regulatory limit | detected | no | — |
| Hardness (total) | 54.6 | 2.7 to 54.6 | mg/L | — | No regulatory limit | detected | no | — |
| 1,4-Dioxane | 0.96 | ND to 0.96 | µg/L | 1.0 | NYS MCL | detected | no | — |
| PFOS | 2.47 | ND to 2.47 | ng/L | 10 | NYS MCL | detected | no | — |
| Lindane | 0.078 | ND to 0.078 | µg/L | 0.2 | EPA MCL | detected | no | — |
| Heptachlor | 0.057 | ND to 0.057 | ng/L | 400 | EPA MCL | detected | no | — |
| Formaldehyde | 10.4 | ND to 10.4 | µg/L | 50 | EPA MCL | detected | no | — |
| Hexavalent Chromium | 7.3 | ND to 7.3 | µg/L | — | No regulatory limit | detected | no | — |
| PFBA | 6.44 | ND to 6.44 | ng/L | — | No regulatory limit | detected | no | — |
| PFHxS | 2.21 | ND to 2.21 | ng/L | — | No regulatory limit | detected | no | — |
| PFPeA | 3.59 | ND to 3.59 | ng/L | — | No regulatory limit | detected | no | — |
| HFPO-DA | — | ND to ND | µg/L | — | EPA MCL of 0.010 µg/L takes effect 2029; no limit in force | not-detected | no | 22 |
| PFNA | — | ND to ND | µg/L | — | EPA MCL of 0.010 µg/L takes effect 2029; no limit in force | not-detected | no | 22 |
| PFBS | — | ND to ND | µg/L | — | No regulatory limit | not-detected | no | 22 |

## Sources

- South Huntington Water District 2025 Annual Water Quality Report: https://www.shwd.org/wordpress/wp-content/uploads/2026/05/SHWD-2025-Water-Quality-Report.pdf
- EPA UCMR 5 PFAS results, 2023–2025 (entry-point samples): https://www.epa.gov/dwucmr/occurrence-data-unregulated-contaminant-monitoring-rule

## EPA compliance record (suppliers serving this community's ZIP codes)

| System | EPA ID | Violations | Health-based | All time | Window | EPA report |
|---|---|---|---|---|---|---|
| Suffolk County Water Authority | NY5110526 | 3 | 0 | 7 | 2022–2026 | https://echo.epa.gov/detailed-facility-report?fid=NY5110526 |
| South Huntington Water District | NY5103263 | 39 | 0 | 40 | 2022–2026 | https://echo.epa.gov/detailed-facility-report?fid=NY5103263 |
| Greenlawn Water District | NY5103271 | 78 | 0 | 79 | 2022–2026 | https://echo.epa.gov/detailed-facility-report?fid=NY5103271 |
| Dix Hills Water District | NY5103276 | 78 | 0 | 83 | 2022–2026 | https://echo.epa.gov/detailed-facility-report?fid=NY5103276 |

## Notes on this data

- Public-water figures are annual results published by the water supplier in its Annual Drinking Water Quality Report (CCR), reported across all wells feeding a distribution area. They describe water leaving the supplier, not the tap in a specific home.
- Private wells are not covered by any public report. Well owners need their own test.
- Status compares the reported average (or the range high where no average is published) to the regulatory limit. 'exceeds' is a numeric comparison, not a regulatory violation finding; see violationFlag for what the supplier reported.
- epaSystems lists the public water systems that report serving this community's ZIP codes (EPA UCMR 5 ZIP list) with their EPA SDWIS violation counts. Counts are compliance events, not contaminant levels.
- publicWaterCoverage: share (0-1) of the community's land inside a public water system service area, from the NYS DOH boundaries EPA publishes; >=0.9 is shown as public water, <=0.1 as private wells, between as mixed.
- areaAssignment: 'inferred' means the SCWA distribution area was taken from neighboring mapped communities, not read from SCWA's map; confirm with SCWA's address lookup.
- dataTier: 'report' = rows from the supplier's annual water quality report; 'epa' = EPA-reported lead and PFAS sampling results so far; 'none' = no public supplier mapped (private wells).
- peakAboveLimit marks a contaminant whose highest single sample was above the limit even though its average was not. Compliance is judged on averages; peaks show what some homes may have received at times.
- Units: µg/L = micrograms per liter = parts per billion; mg/L = milligrams per liter = parts per million. ND = not detected.

## What this means for treatment

For South Huntington, the numbers point first to under-sink reverse osmosis and whole-house carbon filtration: dissolved contaminants close to their limits.

- **Under-Sink Reverse Osmosis** (recommended): Dissolved contaminants close to their limits. Nitrate averaged 7.9 mg/L with samples up to 7.9 against a 10 mg/L limit — the closest number to its limit here. It passes straight through carbon; reverse osmosis is designed to reduce it at the tap. PFOA/PFOS reached 2.47 ng/L (ppt) in at least one sample — under New York's 10 ppt limit. Whether an under-sink reverse osmosis model reduces PFOA or PFOS depends on that model's certification or performance data sheet. Sodium averaged 21.9 mg/L, above the 20 mg/L level New York flags for sodium-restricted diets. Hexavalent chromium averaged 7.3 µg/L; there is no federal limit for chromium-6 itself, and reverse osmosis reduces it. The supplier's 90th-percentile lead result was 0.0013 mg/L (1 ppb) against the 15 ppb action level. Lead enters water from a home's own service line and fixtures, so the system figure says little about any one house; a filter certified for lead (NSF/ANSI 53) or reverse osmosis at the kitchen tap reduces it at the point you drink.
- **Whole-House Carbon Filtration** (recommended): Solvent traces and chlorine in the supply. Free chlorine averaged 1.5 mg/L at the entry point (limit 4), the residual that gives tap water its pool taste and dries skin and hair. Solvent traces were detected: Trichloroethene (TCE) up to 1.7 µg/L, Tetrachloroethene (PCE) up to 0.54 µg/L, 1,1,1-Trichloroethane up to 0.84 µg/L, cis-1,2-Dichloroethene up to 4.4 µg/L (limit 5 each). Whether a whole-house carbon model reduces those solvents is on that model's data sheet.
- **Whole-House + Softener Combo** (not needed): Hardness 54.6 mg/L, about 3.2 grains per gallon. At 54.6 mg/L (3.2 gpg) the water is soft. A softener is not needed.

## Test your own water

A utility report describes the supply, not your tap, and does not cover private wells. Fieldstone Water Co. offers a free in-home water test across Long Island: call 516-43WATER (516-439-2837) or book at https://www.fieldstonewater.com/free-water-test.

---
Compilation © Fieldstone Water Co., licensed CC BY 4.0 (the underlying public records are not ours to copyright): reuse with attribution and a link to https://www.fieldstonewater.com/water/south-huntington, keeping each figure's source citation. Text and explainers all rights reserved. https://www.fieldstonewater.com/terms#data-license