Public water system · EPA ID NY5103705
Riverhead Water District: Water Quality and EPA Record
Riverhead Water District serves about 35,000 people from groundwater wells in Aquebogue, Calverton, Riverhead, Speonk, Wading River. EPA lists 3 violations for it in 2022–2026, 1 of them health-based (4 on file all time). In EPA's 2023–2025 PFAS testing, PFOA reached 4 ppt and PFOS 5.2 ppt at an entry point, against New York's 10 ppt limit, and EPA's 4.0 ppt limit, with federal compliance due April 26, 2029. Its 2025 annual water quality report is transcribed below.
Annual report
2025 Annual Water Quality Report
30 result rows plus 1 unregulated-contaminant rows transcribed from the supplier’s report. Service area as stated: The source of water for the District is groundwater pumped from fifteen (15) active wells located throughout the community that are drilled into the Glacial and Magothy aquifers beneath Long Island. The District holds an additional well, located within the former Northrup Grumman property in Calverton in reserve, due to NYSDEC restrictions. The population served by the Riverhead Water District during 2025 was approximately 36,000. The total amount of water withdrawn from the aquifer in 2025 was 2.629 billion gallons, of which approximately 96.6 percent was billed directly to the residents of the District. New concrete storage tank in Wading River.. Lead 90th percentile: 2.0 ug/l.
- Iron row marked Violation 'Yes' (ND - 0.92 mg/l vs MCL = 0.3, sample date 12/12/25). Page 2: 'We are pleased to report that our drinking water is safe and meets all Federal and State requirements with the exception of iron.' Footnote (4) explains iron health effects and that the District adds a sequestering agent. No formal Notice of Violation text is printed. (12/12/25)
Community pages with the full table
PFAS testing · EPA UCMR 5
What EPA’s 2023–2025 PFAS sampling found
10 entry points sampled from 2023-06-14 to 2024-05-03. 4 of 30 analytes detected. Results are for water leaving each well field before blending, so they show what individual sources carry, not the tap.
| Analyte | Highest result | Detections | Limit (NY / EPA 2029) | Where highest |
|---|---|---|---|---|
| PFOS (about this substance) | 5.2 ppt | 1 of 20 | 10 ppt / 4 ppt | Well 5-1 & 5-2 TP |
| PFOA (about this substance) | 4 ppt | 1 of 20 | 10 ppt / 4 ppt | Well 5-1 & 5-2 TP |
| PFHxA (about this substance) | 3.3 ppt | 1 of 20 | none | Well 5-1 & 5-2 TP |
| PFPeA (about this substance) | 3.2 ppt | 1 of 20 | none | Well 5-1 & 5-2 TP |
EPA record
Violations, 2022–2026
- Violations 2022–2026
- 3
- Health-based
- 1
- All time on file
- 4
- Most recent
- 2023-07
Lead 90th percentile reported to EPA: 2 ppb (2025–2027); 2 ppb (2022–2024); 1 ppb (2019–2021); 2 ppb (2016–2018) against the 15 ppb action level.
Compliance counts are EPA Safe Drinking Water Information System records pulled directly from EPA. Most violations are monitoring or reporting lapses, not unsafe water; health-based violations (a contaminant limit, disinfectant level, or treatment technique) are counted separately. A system listed for a ZIP code may serve only part of it.
Violation history
What the violations were
1 of the events on record are health-based (a contaminant limit, disinfectant level, or treatment technique). The rest are monitoring or reporting lapses.
| Period | Type | Contaminant / rule | Health-based |
|---|---|---|---|
| 2023-07-01 to 2023-09-30 | Maximum contaminant level | Nitrite | Yes |
| 2023-07-01 to 2023-09-30 | Monitoring and reporting | Nitrates | No |
| 2022-04-01 to 2022-04-30 | Monitoring and reporting | Chemical contaminants (Phase II/V) | No |
| 2010-01-01 | Other | Consumer confidence report | No |
Service area
Where Riverhead Water District delivers water
- Wading River (11792)
- Riverhead (11901)
- Aquebogue (11931)
- Calverton (11933)
- 11947
- Speonk (11972)
Start here
On Riverhead Water District water? Find out what reaches your tap.
Supplier reports and EPA records describe the system, not your home. A free in-home test from Fieldstone screens your actual water at the tap and tells you when a certified laboratory test is the right next step.